Troubleshooting
Common Errors
Error Code 0x04 - Path Segment Error:
- Invalid tag path specified
- Check tag names in PLC program
- Verify tag paths match exactly (case-sensitive)
- Ensure tag exists in controller
Error Code 0x08 - Service Not Supported:
- ControlLogix/GuardLogix: Connected to wrong slot
- Verify processor slot number in backplane
- Check backplane configuration in adapter script
Connection Timeouts:
- Scan interval too high for controller
- CompactLogix has short timeout (~128ms)
- Try reducing scan-interval to 0.1
- Note: Lower scan interval may increase PLC load (test carefully)
No Data Appearing:
- Verify tags exist in PLC program
- Check tag paths are correct (case-sensitive)
- Test with simpler configuration first
- Use RSLinx or similar tool to verify tags are accessible
Wrong Controller Type:
- Verify you're using the correct adapter
- MicroLogix: NOT supported with this adapter (use Modbus if available)
- SLC500: Use the dedicated Allen Bradley SLC500 adapter instead